Instruction Manual
HI 8001 & HI 8002
Panel-mounted and Wall-mounted
Fertigation Controllers
Manufacturers since 1978
These Instruments are in
Compliance with the CE Directives
Przeglądanie stron 0
1 2 3 4 5 6 ... 87 88

Podsumowanie treści

Strona 1 - Fertigation Controllers

1Instruction ManualHI 8001 & HI 8002Panel-mounted and Wall-mountedFertigation ControllersManufacturers since 1978These Instruments are inComplianc

Strona 2 - TABLE OF CONTENTS

103.3 FERTILIZATION CONTROLFertigation Controller can use up to 4 fertilizer tanks.Each irrigation program can specify the percentage for each type of

Strona 3

11AGES). For each individual sector’s pH average see panel C 24 (SECTORAVERAGES). All pH averages can be deleted manually or at specified time ofday u

Strona 5 - 2 GENERAL DESCRIPTION

13opening and closing of a valve through which a neutral solution is circulated.The amount of neutral solution added is relative to the opening of the

Strona 6 - 3 FUNCTION DESCRIPTION

14can compensate for changes in the process variable (measurement) and is par-ticularly good for slowly moving processes. When a change occurs in the

Strona 7

15- To erase all statistics, use panel S 61 (ERASE STATISTICS). Statistics indi-cates pH and conductivity averages for all irrigation programs and sec

Strona 8

163.10 LOGGING FUNCTIONSThe Fertigation Controller has the capability to log the most important occurredevents and values of different parameters that

Strona 9

174 USER INTERFACEThe Fertigation Controller’s user interface consists of a 4 x 20 character LCDand a 23-key keyboard.Keyboard structure.4.1 OPERATING

Strona 10

18different controller entities (programs, sectors, fertilizers etc.) within the samepanel.- LEFT and RIGHT ARROWS KEYS can be used to move the cursor

Strona 11

19- LEFT, RIGHT arrow keys allow navigation within the currently focuseddata object. If the cursor exceeds the boundaries of the data object then thef

Strona 12

2Dear Customer,Thank you for choosing a Hanna Product. Please read this instructionmanual carefully before using the instrument.This manual will provi

Strona 13

204.2 PANEL BROWSING METHODSIn consulting mode, two browsing methods are available to view each of the 62panels (screens) of the Fertigation Controlle

Strona 14

2111 SOL RAD EXTENS 40 PH CONTROL12 MAN CORRECTION 41 COND CONTROL13 TOTAL CORRECTION 42 CORRECTIONS14 SECTOR STATE 43 SOLAR RAD IRRIG15 - 44 -16 FER

Strona 15

225 PANEL DESCRIPTION5.1 GENERAL CONSULTINGThe following panels C 01 through C 29 are for the general consulting ofcontroller settings and current m

Strona 16

23Although access to the controllers features are denied, the functionality of thecontroller is not directly effected if a password authentication seq

Strona 17 - 4 USER INTERFACE

24NOTE:- If the user is logged in and the operational mode is CONSULTING MODE,this panel can be accessed anytime and from any panel using the HOME

Strona 18

255.2.1 PROGRAM STATE – C 03PROG 08 ACTIVEStarted by Solar RadRepeat 02/05 13:15PROGRAM STATE C03The purpose of this panel is to allow the user

Strona 19

26REMINDER: In CONSULTING MODE the ESC key can be used as a short-cut key to access this panel from any panel.5.2.2 PH STATE – C 04Prog 08 Ref=06.4

Strona 20

27and is not program specific.S in = Real time value of EC input sensor. This is an option sensor input tomeasure the conductivity of the incoming wat

Strona 21

28DayIndicates if the selected program is set to run on a daily schedule.PeriodIndicates if the selected program is set to run on a yearly schedule.Sy

Strona 22 - 5 PANEL DESCRIPTION

29This panel displays the current irrigation state of the indexed program. Time orvolume can control irrigation and the above panel displays the set v

Strona 23 - GENERAL INFO C01

35.4 Alarms Consulting ... 375.5 Log Consulting ...

Strona 24 - SENSORS STATE C02

305.2.9 MAN CORRECTION – C 12Prog 08 +015% +00:05:55 13:15MAN CORRECTION C12This panel displays how much the programmed irrigation parameters

Strona 25 - PROGRAM STATE C03

315.2.11 SECTOR STATE – C 14Prog 08 Sect 21/21Set 00:10:30+009:45Done 00:03:10 13:15SECTOR STATE C14This panel displays the state of each secto

Strona 26

32This panel displays the set and current amount of fertilizer used for a specificprogram. The Fertigation Controller controls the dosing of 4 fertil

Strona 27

33PauseThe set pause time value for the indexed agitator of the selected program.System clockNOTE: The agitator’s working time values can be specified

Strona 28

345.3 STATISTICS CONSULTING5.3.1 TOTAL ACCUMUL – C 19From: 09-26 13:37;120007654L 13:15TOTAL ACCUMUL C19This panel provides a total

Strona 29 - SOL RAD EXTENT C11

355.3.3 SECTOR ACCUMUL – C 21From: 09-26 13:37;12000:00:17 Sect 01/01 13:15SECTOR ACCUMUL C21This panel provides a total (in time or v

Strona 30

365.3.5 PROGRAM AVERAGES – C 23From: 09-26 13:37;1205.3pH Prog 0106.7mS 13:15PROGRAM AVERAGES C23This panel provides a pH & EC avera

Strona 31

375.4 ALARMS CONSULTING5.4.1 ACTIVE ALARMS – C 25Low level fert: 4ACTIVE Alarm26-12 14:36:22 13:15ALARM 02/07 C25This displays the active alarms

Strona 32 - AGITATOR STATE C17

38pressed the Fertigation Controller will search for the logged data. If no data isfound the panel is shifted to C 28 (LOG) and “no records found” is

Strona 33 - PROG LAST START C18

39SET key or via panel S 59 (SET LOG LEVELS). The UP and DOWN arrow keysare available to move between log records in a “select previous/next” manner.T

Strona 34

41 THEORY OF FUNCTIONIrrigation is one of the most important operation in agriculture. With properirrigation the quality and quantity of crops can be

Strona 35

405.7 PROGRAM SETTINGS5.7.1 ACTIVE TIMETABLE – S 31Between Prog 07Date: 01-04 31-10Time: 07:00 23:00ACTIVE TIMETABLE S31This panel allows the u

Strona 36

41(for more details see Section 3.1 and Appendix 3):Work dayThe number of consecutive workdays.Program NumberReflects the selected program (can be sel

Strona 37

425.7.4 START CONDITIONS – S 34Time cond y Prog 07Solar rad NExt tank: -- Link 02START CONDITION S34Using this panel we can set up how a particular p

Strona 38

43allows the setting of the following parameters:Program NumberReflects the selected program (can be selected only inside panel C 03). SeeSection 5.2.

Strona 39 - SET DATE & TIME S30

44mode, see panel S 53 (IRRIG CTRL MODE). The program number indexes thispanel (for more details see Section 3.1 and Appendix 3). This panel display

Strona 40

455.7.9 SET FERTILIZERS – S 39 Prog 07Fer1=020% Fer2=055%Fer3=060% Fer4=040%SET FERTILIZERS S39The fertilizer dosing is controlled b

Strona 41 - SET PRIORITY S33

46Alarm thresholdSelectable pH control alarm threshold represents the time interval (mea-sured in the Fertigation Controller’s control cycles) conside

Strona 42 - Prog 07

47fertilization process. The program number indexes this panel. This panel displaysand allows the setting of the following parameters:ManualThe selec

Strona 43

48program. If “Work” and “Pause” are set the agitator will function intermittentlyrelative to the time settings. In this panel the agitator number is

Strona 44 - SET SECTORS S38

495.8 MANUAL COMMANDS5.8.1 MANUAL START – S 47Active program: 03Start program: -- ?PROG MAN START S47Each program can be manually started using thi

Strona 45 - Prog 07

52 GENERAL DESCRIPTIONThe Fertigation Controller is a micro-processor-based system used in fertiliza-tion and irrigation control for greenhouses or op

Strona 46

50Y (yes) can be entered next to the selected condition to change the controllerstate. Only the Y (yes) key will have effect in activating the appropr

Strona 47

51Ctrl in Pre / PostPress Y (yes) then ENTER to control pH prior and after irrigation.Use acid in pHCtrlPress Y (yes) or N (no) then ENTER to control

Strona 48 - FILTERS CTRL S46

525.9.4 CALIBRATE SENSORS – S 54 Channel: 01Now: 02.3 Ref: 02.5Status: First StageCALIBRATE SENSOR S54The sensor calibration procedure consist

Strona 49 - STOP - WORK

53SensNr = The selectable number of pH sensors in the system (1 to 2).SensNr = The selectable number of EC sensors in the system (1 to 3).SDifThe maxi

Strona 50 - Ctrl in Pre/Post Y

54ECkFactory amplification setting for EC control.ECTiIntegral constant for EC control. Setting the value to 99.9 minutes effec-tively disables the in

Strona 51 - Volume control: N

55corded and can be inspected at the same time. Alarm events are stored regard-less of log level and can be inspected using panel C 27 (ANOMALY). Pa

Strona 52 - Channel: 01

565.9.11 ERASE STATISTICS – S 61 Erase all: - On overflow: YDaily at hour: 00:01ERASE STATISTICS S61With this panel it is possible to erase stored

Strona 53

576 CALIBRATION PROCEDURES6.1 SENSOR CALIBRATION PROCEDUREThe purpose of calibrating the Sensor’s used in conjunction with the FertigationController i

Strona 54

586.2 PID TUNING PROCEDUREFor the PID controller, we have three working modes:1. With PID regulation algorithm (Proportional, Integrative and Derivati

Strona 55 - SET PASSWORD S60

596.2.1 PID TUNING PROCEDUREDue to the fact that the pH and EC controls function with minimal error at thecontrol output value, the PID controller mus

Strona 56 - Erase all:

63 FUNCTION DESCRIPTIONIn this chapter the main functions of the Fertigation Controller are presented. Fora better understanding see the typical insta

Strona 57 - 6 CALIBRATION PROCEDURES

60A. NECESSARY STEPS FOR TUNING THE PID CONTROLLER FOR PH AD-JUSTMENT1. The pH of the water source used for irrigation is measured. When this value is

Strona 58

6110. At the end of the program consult the log table. Write down in a table thevalues for the pH sensor and the time when the reading was done (see S

Strona 59

62- Total number of sectors = 1- Irrigation time = 15 minute2. Go to panel S 38 (SET SECTORS) and check the above settings. If they aredifferent adjus

Strona 60

63NOTE: The period of time for Irrigation time (15 minute default) - panel S 37(PRE/POST IRRIG) - can be modified (increased or decreased), if theproc

Strona 61

64- The control function remains constant; however, a steady state offset ispresent meaning that the set point is never completely maintained.4. INTEG

Strona 62

65sensor #1) is outside of the allowable dead band determined by the specified pHReference value together with the pH min and pH max offset limits. Th

Strona 63

668 TROUBLE SHOOTING GUIDETHE CONTROLLER DOES NOT FUNCTIONCheck to insure that the proper voltage is applied to the controller. After con-necting the

Strona 64 - 7 ALARM DESCRIPTION

67occurred that may not be correctable by the type and amount of acid (or base)being used. If the problem persists after checking the process pH and a

Strona 65

689 ELECTRICAL DIAGRAMS

Strona 67

7- The accumulated solar radiation starting level value is used as a thresholdvalue for the accumulated solar radiation. When the accumulated solarrad

Strona 69

71POWERBOARDEXTENSIONBOARDMAINBOARD

Strona 70

72APPENDIX 1- KEYBOARD OPERATING MODESCONSULTING MODE:- arrow keys can be used to navigate inside the currently focused object- ESC key can be used as

Strona 71

73APPENDIX 2 - OUTLET ASSIGNMENT TABLEOUTLET NUMBER ASSIGNED ELEMENT08 Filter1 35 SECTOR VALVE 1209 Filter2 36 SECTOR VALVE 1310 pH 37 SECTOR VALVE 14

Strona 72

74APPENDIX 3 - GRAPHICAL EXPLANATION

Strona 75

77APPENDIX 4 - LIST OF PANELSGeneral InfoWORK Anomalies 00Prog 08 06.4pHSect 07 02.1mS 13:15GENERAL INFO C01Active Program: 0406.3pH 1200W/m2

Strona 76

78Prog 08 Time Y Day Y Period Y 13:15WORK TIME COND C08Prog 08 Priority 05Conflict Programs 02 13:15PRIOR & CONFLICT

Strona 77 - APPENDIX 4 - LIST OF PANELS

79Prog 02 Fert 02 Set 40%Current 20% 13:15FERTILIZ STATE C16Prog 08 Agitator 01Work 00:03 WORKPause 00:02 13:15AGITATOR STATE C1

Strona 78

8SOLAR RADIATION FACTOR:- This option can be set using panel S 42 (CORRECTIONS). This factoraffects the irrigation time or volume extension in accorda

Strona 79 - Program Settings

80Prog 07Repeats 04 Pause 00:30:00PROGRAM REPEATS S36 Prog 07 PreIrrig: 000:00:05PostIrrig: 000:00:05PRE/POST IRRIG S37Valve 05 Pr

Strona 80 - Prog 07

81Pre 00:33 Prog 08Work 00:10Pause 00:05SET AGITATORS S45Link 05 Filter 01Clean on alarm: YClean time: 01:01:02FILTERS CTRL S46Controlle

Strona 81 - Controller Settings

82Ctrl on pH alarm: YIrrig on pH alarm: Y Ctrl on EC alarm: YALARM BEHAVIOR S52Volume control: N Time control: YIRRIG CTRL MODE S53 Channel: 01N

Strona 82 - Channel: 01

83Disable password: NNew password: ---SET PASSWORD S60Statistics ConsultingFrom: 09-26 13:37;120007654L 13:15TOTAL ACCUMUL C19Fro

Strona 83 - Statistics Consulting

84Controller LoggingExt state:ACTIVEProg State changed.18-08 15:05:30 15:05Log 0012 Lev 03 C28Manual CommandsActive program: 03Start program: -- ?PRO

Strona 84 - Manual Commands

85APPENDIX 5 - INSTALLATION BLOCK DIAGRAM

Strona 86

87Recommendations for userBefore using this product, make sure that it is entirely suitable for the environment inwhich it is used.Operation of this i

Strona 87 - WARRANTY

88www.hannainst.comMAN800107/03

Strona 88

9sectors using one of the following ways:- Manually- Every day at specified hour- Automatically when the accumulations counter value overflows3.2 COND